BACnet/IP Controller 750-830 51
Hardware
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
3.1.3.4 Indicators
The operational status for the fieldbus controller and the node is indicated by
light emitting diodes (LEDs).
These are multi-colored (red, green or red-green (=orange)).
24V 0V
++
01
02
ETHERNET
C
D
B
A
C
B
A
24V 0V
++
01
02
C
D
B
A
C
B
A
LNK
ACT
BT
MS
I/O
BACnet/IP
NS
USR
A
B
Fig. 3-2: Indicators 750-830 g083002x
Tab. 3-3: LED Signals
LED Color Meaning
LNK/ACT
Off
Green
Green flashing
Network connection and activity at Port 1
BT
Off
Green
Green flashing
Red
BACnet data traffic
MS
Off
Green
Green flashing
Red, flashing
Red
Red-green (orange) flashing
System operating mode
NS
Off
Green
Green flashing
Red flashing
Red
Red-green (orange) flashing
IP address configuration and communication
I/O Red/green (orange)
The "I/O" LED indicates the operational status
of the node and signals any errors.
USR Red/green (orange)
The "USR" LED can be controlled by a user
program.
A Green Status of the system power supply
B Green Status of the power supply for the power contacts
Additional Information
The evaluation of the LED signals is described in more detail in section 3.1.9,
"LED Signals".