NETWORK CONNECTION: PROVIDE RJ-45 ON TELEPHONE BOARD FOR SYSTEMS
NETWORK CONNECTION.
POWER SUPPLY XFMR: PROVIDE 75VA, 120VAC TO 24VAC TRANSFORMER,
'FUNCTIONAL DEVICES' MODEL #PSH75ANW, WITH ENCLOSURE FOR SYSTEM
POWER.
TALISMAN MASTER CONTROLLER: CONFIGURE PER MANUFACTURERS
INSTRUCTIONS.
T-STAT CONTROLLER: CONFIGURE PER MANUFACTURERS INSTRUCTIONS.
PROVIDE PERMANENT LABEL INDICATING RTU SERVED.
DUCT TEMPERATURE SENSOR:
ZONE TEMPERATURE SENSOR:
ROOF TOP UNIT: CONNECT T-STAT CABLE TO APPROPRIATE TERMINALS IN RTU
CONTROL SECTION.
LIGHTING CONTROLLER: CONFIGURE PER MANUFACTURERS INSTRUCTIONS.
OUTDOOR LIGHT SENSOR: OUTDOOR RATED, ANALOG PHOTOCELL IN WATER
PROOF BOX.
LIGHTING CONTACTOR CABINET: ENCLOSURE FOR LIGHTING RELAYS AND
LIGHTING CONTACTORS. SIZE AS REQUIRED TO HOUSE ALL COMPONENTS.
LIGHTING RELAY: SPDT PILOT RELAY, 'FUNCTIONAL DEVICES' MODEL #RIB2421C,
WITH 24VAC COIL & 10A CONTACTS AT 120 VOLTS.
LIGHTING CONTACTOR: LIGHTING CONTACTOR, 'GE' MODEL #CR460, WITH 30A,
NORMALLY CLOSED CONTACTS AND 120VAC COIL.
INTERIOR OVERRIDE SWITCH: TWO PUSHBUTTON OVERRIDE SWITCH FOR
INTERIOR LIGHTING. PROVIDE PERMANENT LABELS STATING "EMPLOYEE
LIGHTING OVERRIDE" & "CUSTOMER LIGHTING OVERRIDE".
EXTERIOR OVERRIDE SWITCH: AUTO-OFF TIMER, 'INTERMATIC' MODEL #FF32H,
WITH 2 HOUR TIME CYCLE, NO HOLD FEATURE, SPDT SWITCH AND 20A, 120VAC
CONTACTS. PROVIDE PERMANENT LABELS STATING "EXTERIOR SIGNAGE
OVERRIDE" & "EXTERIOR LIGHTING OVERRIDE".
UN-SWITCHED CONDUCTOR: CONNECT AHEAD OF CONTACTS FOR CONSTANT
HOT TO EMERGENCY LIGHTS OR EXHAUST FAN.
SYSTEM GROUND: PROVIDE #12 CU GROUND PER SHOP DRAWINGS.
DEVICE JUMPERS: SET DEVICE JUMPERS PER SHOP DRAWINGS.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
L PROVIDE BREAKER WITH "LOCK-ON" DEVICE
C CIRCUIT THRU CONTACTOR FOR EMS CONTROL
G G.F.C.I. CIRCUIT BREAKER
H CIRCUIT BREAKER SHALL BE HACR RATED
MARK TYPE
DESCRIPTION MODEL USAGE
4P / 24AWG CABLE UNSHIELDED SOLID
COPPER CONDUCTORS
BERK-TEK
CAT5E
NETWORK
CABLE
1P / 22AWG CABLE SHIELDED SOLID
COPPER CONDUCTORS (BLACK / RED)
BELDEN
6520FE
ALL
SENSORS
3C / 22AWG CABLE SHIELDED
STRANDED TINNED COPPER
CONDUCTOR (BLACK / RED / CLEAR)
BELDEN
8771
BACNET
BUS WIRE
8C / 18AWG THERMOSTAT CABLE
INCLUDING 24VAC FROM RTU
T-STAT
T-STAT
WIRE
14AWG THHN WIRE THHN
24V
POWER
12AWG LINE (120V) VOLTAGE WIRE
THWN
GENERAL
POWER
A
B
C
D
E
F
T-STAT CONTROLLER:
OCCUPIED COOLING:

OCCUPIED HEATING:
UNOCCUPIED COOLING:
UNOCCUPIED HEATING:
LIGHTING CONTROLLER:
R1: EMPLOYEE LIGHTING: (50% OF SALES, ASSOCIATE RESOURCES, OFFICE,
BATHING & DRYING) - ON FROM 6:00 AM TILL 11:59 PM.
R2: CUSTOMER LIGHTING: (50% OF SALES & FISH LIGHTS) - ON 15 MINUTES
BEFORE STORE OPEN AND OFF 30 MINUTES AFTER STORE CLOSURE.
VERIFY OPENING SCHEDULE WITH STORE MANAGER FOR FINAL SETUP.
R3: EXTERIOR SIGNAGE: (PETSMART & GROOMING SIGNS) - ON FROM DUSK
TILL 12:01 AM AND 5:00 AM TILL DAWN.
R4: EXTERIOR LIGHTING: (BUILDING & SITE LIGHTS) - ON DUSK TILL DAWN
VIA EXTERIOR PHOTOCELL.
OVERRIDE SWITCHES:
OVERRIDE PUSH BUTTONS & TIMER SWITCHES SHALL TURN LIGHTS ON FOR
TWO (2) HOURS, THEN AUTOMATICALLY REVERT TO SCHEDULED STATUS.
+ - + - + - + - + - + -
AI1 AI2 DI1 AI3 DI2 AOP
DO- DI+ C
BUS
24V C R1 R2 R3 R4 R5 R6
DIGITAL OUTPUTS
+ - + - + - + 24/- + - + -
ZONE SUPPLY FANP MA D IN AOP
DI+ C
BUS
R C G Y1 Y2 W1/B W2 0
FAN COOL HEAT
DO-
OUTPUT #R4
OUTPUT #R3
OUTPUT #R2
OUTPUT #R1
24VAC POWER
24VAC COMMON
HEAT PUMP REVERSING VALVE
CALL FOR HEAT: STAGE #2
CALL FOR HEAT: STAGE #1
CALL FOR COOL: STAGE #2
CALL FOR COOL: STAGE #1
FAN CONTROL
RTU: 24VAC COMMON
OLS
DTS
ZTS
RTU: 24VAC POWER
PWR -/B
PWR +/B
PWR -/A
PWR +/A
POWER INPUT A
POWER INPUT B
RS - 485 PORT #2 (BACNET)
RS - 485 PORT #1 (MODBUS)
PULSE METER INPUT
C
DI/+
D0/-
C
DI/+
D0/-
-
+
10/100 ETHERNET #2
(SOUTHBOUND)
10/100 ETHERNET #1
(NORTHBOUND)
USBA
KEYPAD
DISPLAY
CONSOLE PORT
SW1
RESET
SW2
COLDSTART
MAC ADDRESS
BACKUP BATTERY
ALARM
STATUS
POWER OK
BLUETOOTH
MODULE
SDHC
CARD
XBEE
MODULE
SN#
BACNET OUTPUT
BACNET INPUT
BACNET COM
RJ-45
NEUTRAL
120VAC
+ -
MAC ADDRESS
120VAC
24VAC
BACNET OUTPUT
BACNET INPUT
BACNET COM
BACNET OUTPUT
BACNET INPUT
BACNET COM
DUCT
24VRJ-45
TALISMAN
RTU
120V
RTU
DUCT
S S
C
C
R
120V
SIGNAGE
EMPLOYEE
CUSTOMERC
C
EMPLOYEE
R
R
T
EMPLOYEE
CUSTOMER
EMPLOYEE
LIGHTING OVERRIDE
CUSTOMER
LIGHTING OVERRIDE
A. THE ENERGY MANAGEMENT SYSTEM (EMS) IS A BACNET BASED SYSTEM FROM
QUEST CONTROLS INC. THE SYSTEM IS DESIGNED BY QUEST CONTROLS ON A
PROJECT SPECIFIC BASIS. SHOP DRAWINGS REVIEWED BY THE
PROFESSIONAL OF RECORD IS REQUIRED.
B. ALL EMS EQUIPMENT SHALL BE FURNISHED AND INSTALLED AS INDICATED IN
EQUIPMENT SCHEDULE. MECHANICAL CONTRACTOR MUST ORDER FROM
QUEST CONTROLS, NO EXCEPTIONS. CONTACT QUEST CONTROLS ORDERING
CONTACT FOR PRICING. COORDINATE DELIVERY WITH QUEST. SEE SHEET F2.0
FOR CONTACT INFORMATION. ELECTRICAL CONTRACTOR SHALL FURNISH
AUXILIARY EQUIPMENT AS SHOWN OR EQUAL.
C. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING ALL CONDUIT,
WIRE, PULL BOXES, AND JUNCTION BOXES REQUIRED FOR A COMPLETE
INSTALLATION.
D. WIRING SHALL BE CONCEALED WHERE POSSIBLE. WHEN NOT SUBJECT TO
DAMAGE, AND LOCAL CODES PERMIT, WIRING MAY BE RUN OPEN, SECURED
AT REGULAR INTERVALS. ALL EXPOSED CABLES TO BE RUN AND CONCEALED
IN THE ANGLE OF THE BAR JOIST AND NEATLY WIRE-TIED TO BAR JOIST, NOT
DRAPED BETWEEN BRACES. SAGGING WIRES ARE NOT PERMITTED.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR GROUND TO EMS
CONTROLLER. ALL SHIELDED WIRE MUST BE TERMINATED TO GROUND AT
THE QUEST PANEL END ONLY. AT SENSOR, CUT SHIELD OFF AND TAPE END.
F. ELECTRICAL CONTRACTOR SHALL SET DEVICE ADDRESSES PER QUEST
INSTALLATION DRAWINGS.
G. ALL WORK SHALL CONFORM WITH THE LOCAL, STATE, & NATIONAL
ELECTRICAL CODES. ELECTRICAL CONTRACTOR SHALL PAY FOR ALL
INSPECTIONS AND PERMITS.
H. LOW VOLTAGE CONDUCTORS SHALL MAINTAIN A MINIMUM 1/4" CLEARANCE
FROM POWER CONDUCTORS.
I. ELECTRICAL CONTRACTOR SHALL LABEL ALL WIRES AND CABLES ON BOTH
ENDS.
J. ELECTRICAL CONTRACTOR SHALL SUBMIT RFI THRU PETSMART WEBSITE FOR
ANY QUESTIONS REGARDING EMS SYSTEM DRAWINGS OR INSTALLATION.
K. WHEN THE MECHANICAL & ELECTRICAL CONTRACTOR HAS COMPLETED
INSTALLATION OF THE EMS SYSTEM AND COORDINATED WORK WITH
MECHANICAL CONTRACTOR, THE MECHANICAL & ELECTRICAL CONTRACTORS
SHALL COORDINATE START-UP AND COMMISSIONING WITH QUEST CONTROLS
& PETSMART CONSTRUCTION MANAGER.
24VAC POWER
24VAC COMMON
CR EXTERIOR
T
4
E4.0 SCALE: NONE
T-STAT CONTROLLER
5
E4.0 SCALE: NONE
LIGHTING CONTROLLER
3
E4.0 SCALE: NONE
TALISMAN MASTER CONTROLLER
2
E4.0 SCALE: NONE
EMS ONE LINE DIAGRAM
+-
MARK
NAME
FURNISH
BY
INSTALL
BY
TERMI-
NATIONS
BY
MOUNTING
M.C. E.C. M.C. E.C. M.C. E.C.
NETWORK CONNECTION X X X 1
POWER SUPPLY XFMR X X X 1
TALISMAN MASTER CONTROLLER X X X 1
T-STAT CONTROLLER X X X 1
DUCT TEMPERATURE SENSOR X X X 2
ZONE TEMPERATURE SENSOR X X X 3
ROOF TOP UNIT X X X --
LIGHTING CONTROLLER X X X 1
OUTDOOR LIGHT SENSOR X X X 4
LIGHTING CONTACTOR CABINET X X X 5
LIGHTING RELAY X X X 6
LIGHTING CONTACTOR X X X 6
INTERIOR OVERRIDE SWITCH X X X 7
EXTERIOR OVERRIDE SWITCH X X X 8
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A E
E
FF
E
D D
BACNET OUTPUT
BACNET INPUT
BACNET COM
BACNET OUTPUT
BACNET INPUT
BACNET COM
1. MOUNT ON TELEPHONE BOARD WHERE SHOWN ON ELEVATION "TELEPHONE
BOARD" (2/E3.0).
2. MOUNT IN RTU SUPPLY DUCT AFTER COOLING COIL.
3. PROVIDE J-BOX & 1/2" CONDUIT TO JOIST SPACE OR 6" AFC. MOUNT WHERE
SHOWN AT HEIGHT INDICATED ON "POWER PLAN" (1/E2.0).
4. MOUNT ON ROOF TOP UNIT WHERE SHOWN ON "POWER PLAN" (1/E2.0). MOUNT
FACING NORTH, AIMED AWAY FROM AMBIENT LIGHT.
5. SEE "ONE LINE DIAGRAM" (1/E4.0).
6. MOUNT WITHIN LIGHTING CONTRACTOR CABINET.
7. PROVIDE J-BOX & 1/2" CONDUIT TO JOIST SPACE OR 6" AFC. MOUNT WHERE
SHOWN AT HEIGHT INDICATED ON "LIGHTING PLAN" (1/E1.0).
8. MOUNT NEXT TO ELECTRICAL PANELS. SEE "LIGHTING PLAN" (1/E1.0).
1 2
3
3
4
5
5
6
6
7
8
8
4
9
9
10
11 12
13
13
14
16
17
17
17
17
4
5
6
7
2
1
GENERAL NOTES
ENERGY MANAGEMENT SYSTEM
LEGEND
ENERGY MANAGEMENT SYSTEM
CONTROL SETTINGS
ENERGY MANAGEMENT SYSTEM
KEYNOTES
ENERGY MANAGEMENT SYSTEM
NOTES
PANEL SCHEDULES
EQUIPMENT SCHEDULE
ENERGY MANAGEMENT SYSTEM
C
B
C
B
C
B
B B
SEE SHEET E2.0
FOR NUMBER OF
RTU'S
UTILITY FEEDERS: NEW FEEDER SIZE & ROUTING PER UTILITY REQUIREMENTS.
COORDINATE WITH UTILITY PRIOR TO BID.
UTILITY TRANSFORMER: NEW CONCRETE PAD PER UTILITY REQUIREMENTS
COORDINATE INSTALLATION WITH UTILITY.
SERVICE FEEDERS (200A): NEW (4) #3/0, Cu, XHHW, IN 2" CONDUIT.
METERING EQUIPMENT: NEW 200A METERING EQUIPMENT PER UTILITY
REQUIREMENTS. COORDINATE INSTALLATION WITH UTILITY.
MAIN DISCONNECT: NEW EXTERIOR, NEMA 3R, 200A, FUSED DISCONNECT WITH
(3) 200A LPJ FUSES AND SOLID NEUTRAL.
SERVICE GROUND: NEW SERVICE GROUND. #4 Cu TO WATER MAIN, BUILDING
STEEL, FOOTING GROUND AND GROUND ROD PER NEC.
PANEL "H" FEEDERS (200A): NEW (4) #3/0, (1) #6 GR., Cu, XHHW, IN 2" CONDUIT.
PANEL "H": NEW 480Y/277V PANEL. SEE PANEL SCHEDULE.
XFMR "T1" FEEDERS (70A): NEW (3) #4, (1) #8 GR., Cu, XHHW, IN 1" CONDUIT.
XFMR "T1": NEW 45kVA, NEMATP-1, 480 - 208Y/120V TRANSFORMER.
XFMR "T1" GROUND: NEW #4 Cu GROUND TO BUILDING STEEL PER NEC.
PANEL "A" FEEDERS (150A): NEW (4) #1/0, (1) #6 GR., (1) #6 I.G., Cu, XHHW, IN 2"
CONDUIT.
PANEL "A": NEW 208Y/120V PANEL. SEE PANEL SCHEDULE.
PANEL "B" FEEDERS (150A): SAME AS PANEL "A" FEEDERS, VIA FEED-THROUGH
LUGS IN PANEL "A".
PANEL "B": NEW 208Y/120V PANEL. SEE PANEL SCHEDULE.
CONTACTOR CABINET: NEW NEMA 1, ENCLOSURE FOR LIGHTING CONTACTORS
AND RELAYS. MOUNT ABOVE ELECTRICAL PANELS. SEE EMS DIAGRAMS (E4.0).
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CNTCTR
CABINET
M
PANEL
"B"
PANEL
"A"
GRADE FINISHED FLOOR
ROOF
INTERIOR
EXTERIOR
1
E4.0 SCALE: NONE
ONE LINE DIAGRAM
XFMR
480Y/277V
3/4W
1
2
3
4
7
5
6
7
13 15
16
14
KEYNOTES
ONE LINE DIAGRAM
F.D.S.
PANEL
"H"
8
XFMR
"T1"
9
12
10
11
OUTPUT #R2
OUTPUT #R1
OUTPUT #R3
OUTPUT #R4
6
E4.0 SCALE: NONE
RELAYS & CONTACTORS
H-1
EMPLOYEE
C1
4 POLE
N/C
T4
R4
EMPLOYEE
C2
4 POLE
N/C
H-5
B-4
A-27
A-29
A-31
CUSTOMER
C3
4 POLE
N/C
H-3
B-8
SIGNAGE
C4
4 POLE
N/C
B-2
B-6
EXTERIOR
C5
4 POLE
N/C
H-9
R3
R2
R1
T3
120VAC POWER
120VAC NEUTRAL
24VAC COMMON
24VAC POWER
1211
14
15 TYP.
15
TYP.
MT/JS
Store No. 2521
437 STATE ROUTE 104E
OSWEGO, NY 13126
Job No:
Drawn:
Scale:
Checked:
Sheet No:
14047
R
23 Wayne Ave., Dayton, OH 45402
As indicated
E4.0
MSW
ONE--LINE & DETAILS