BACnet/IP Controller 750-830 117
Programming the PFC Using WAGO-I/O-PRO CAA
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
MODBUS RTU
Click the link "MODBUS RTU" to go to a Web site where you can specify the
settings for the MODBUS/RTU protocol.
On this page, you set the baud rate of 9600 (standard), 19200 or 57600. With
each byte, a parity bit can also be sent. Errors in data transmission are detected
with the aid of the parity bit. A differentiation is made between even (even
parity), uneven (odd parity) and no parity testing (no parity).
Enter the "Slave Device Address" in the range 0-255 and select "Override de-
fault fieldbus settings" in order to assign all modules MODBUS/RTU by de-
fault instead of MODBUS/IP.
Fig. 3-17: Web-based Management System: MODBUS RTU